Raritan PX3-1032

SPHINX i Europa
DK
  • AT
  • BE
  • DK
  • FR
  • DE
  • IE
  • IT
  • NL
  • ES
  • SE
  • CH
  • UK
Produktgrupper > Power Management > Raritan PX3-1032

Raritan PX3-1032

Monitored rack power distribution unit
(0U [vertical], 3.7kVA, 20 outlets)

Raritan PX3-1032
6032_19015.png
6032_19016.jpg
6032_19017.jpg
  • beskrivelsebeskrivelse
  • yderligere informationyderligere information
  • PDFPDF

Monitored rack power distribution unit
(0U [vertical], 3.7kVA, 20 outlets).

INPUT:
230v, 16a - IEC 60309 2P+E 6h 16A plug (2P3W);

OUTPUT:
4@ BS, 16@ C13 outlets;

FEATURES:
Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet;
Color, matrix LCD display : Voltage, current, or active power (per line);
Alarms; Configuration information (name, ratings, IP / Networking information).
Auto-flip orientation.;
Field-Replaceable, hot-swappable network module with 400MHz processor, 16MB NOR Flash, and 64MB SDRAM;
(10/100) Ethernet portRemote network monitoring via HTML, JSON-RPC, SSH, Telnet, MODBUS/TCP, and SNMPv3.
Environmental monitoring [temp/humidity] capable of up to 32 sensors.
Individual outlet numbers labeled on chassis.
Automated deployment via TFTP, DHCP/PXE, SSH(CLI), or USB Flash Drives.
WiFi Capable.
USB Webcam Capable.
iPad/iPhone/Android App.
Max Dimensions 52mm x 43mm x 1298mm (2.1in x 1.7in x 51.1in).
Max Weight TBD.
Maximum ambient temperature 60C at full load.
ProdGrafik

Features

    Energy Metering
    Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor

    Metering Accuracy
    ISO/IEC 62053-21 1%

    Remote Outlet Switching
    No

    Metering per input line
    Yes for all models

    Metering per Branch Circuit Breaker
    No

    Environmental Sensor Ready
    Yes

    Compatible Sensors
    Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure.

    Cascading
    Yes, Max 16 PDUs can be daisy chained using a USB connection.
    Note: Firmware version 3.3.10 or above is required.

    Networking
    10/100/1000 BaseT Ethernet. Optional WiFi (802.11a/b/g/n).

    Onboard Display
    Color, matrix LCD display : Voltage, current, or active power (per line); Alarms;
    Configuration information (name, ratings, IP / Networking information).
    Auto-flip orientation.



Specifications

    Input

      Input Plug
      IEC 60309 2P+E 6h 16A (2P3W)

      Nominal Voltage
      230V

      Maximum Input Current
      16A

      Rated Input Current
      16A

      Power Capacity
      3.7kVA

      Cord Length
      3m



    Output

      Nominal Voltage
      230V

      Receptacles (Output Connections)
      (4) BS1363 BS
      (16) IEC320 C13

      Overload Protection
      NA



    Physical

      Dimensions (WxDxH)
      2.1in x 1.7in x 51.1in; 52mm x 43mm x 1298mm

      Unit Weight
      TBD

      Shipping Weight
      TBD

      Shipping Dimensions
      185mm x 120mm x 1408mm

      Mounting
      RACK-KIT-PX2-1K-ZU



    Environmental

      Operating Temperature/Environment
      60 C

      Operating Relative Humidity
      85%

      Operating Elevation
      0-10000ft



    Conformance

      Regulatory Approvals
      CE



Kunder, der kiggede på dette produkt, kiggede også på
Accept all Reject Configure