Raritan PX3-1842NU-E2N1

SPHINX i Europa
DK
  • AT
  • BE
  • DK
  • FR
  • DE
  • IE
  • IT
  • NL
  • ES
  • SE
  • CH
  • UK
Produktgrupper > Power Management > Raritan PX3-1842NU-E2N1

Raritan PX3-1842NU-E2N1

Monitored rack power distribution unit
(0U [vertical], 7.4kVA, 30 outlets)

Raritan PX3-1842NU-E2N1
6130_19398.png
6130_19399.jpg
6130_19400.jpg
  • beskrivelsebeskrivelse
  • yderligere informationyderligere information
  • PDFPDF

Monitored rack power distribution unit (0U [vertical], 7.4kVA, 30 outlets).


INPUT:
230v, 32a - Hardwired [Unterminated Cord, No Plug];

OUTPUT:
24@ C13 Locking, 6@ C19 Locking outlets;
on 2@ 1-pole, 16a Overcurrent Protectors;

FEATURES:
Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet, per breaker/fuse;
Color, matrix LCD display : Voltage, current, or active power (per line or per breaker);
Alarms;
Configuration information (name, ratings, IP / Networking).;
Field-Replaceable, hot-swappable network module with 400MHz processor, 16MB NOR Flash, and 64MB SDRAM;
(10/100) Ethernet portRemote network monitoring via HTML, JSON-RPC, SSH, Telnet, MODBUS/TCP, and SNMPv3.
Environmental monitoring [temp/humidity] capable of up to 32 sensors.
Individual outlet numbers labeled on chassis.
Automated deployment via TFTP, DHCP/PXE, SSH(CLI), or USB Flash Drives.
WiFi Capable.
USB Webcam Capable.
iPad/iPhone/Android App.
Breaker metering and alarming (0V detection).
Max Dimensions 52mm x 65mm x 1780mm (2.1in x 2.6in x 70.1in).
Max Weight TBD.
Maximum ambient temperature 60C at full load.
ProdGrafik

Features

    Energy Metering
    Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor

    Metering Accuracy
    ISO/IEC 62053-21 1%

    Remote Outlet Switching
    No

    Metering per input line
    Yes for all models

    Metering per Branch Circuit Breaker
    Yes

    Environmental Sensor Ready
    Yes

    Compatible Sensors
    Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure.

    Cascading
    Yes, Max 16 PDUs can be daisy chained using a USB connection.
    Note: Firmware version 3.3.10 or above is required.

    Networking
    10/100/1000 BaseT Ethernet.
    Optional WiFi (802.11a/b/g/n).

    Onboard Display
    Color, matrix LCD display : Voltage, current, or active power (per line or per breaker);
    Alarms;
    Configuration information (name, ratings, IP / Networking information).
    Auto-flip orientation




Specifications


    Input

      Input Plug
      Cord (N/A)

      Nominal Voltage
      230V

      Maximum Input Current
      32A

      Rated Input Current
      32A

      Power Capacity
      7.4kVA

      Cord Length
      3m



    Output

      Nominal Voltage
      230V

      Receptacles (Output Connections)
      (24) IEC320 C13 Locking
      (6) IEC320 C19 Locking

      Overload Protection
      (2) LEGBXA6-16



    Physical

      Dimensions (WxDxH)
      2.1in x 2.6in x 70.1in;
      52mm x 65mm x 1780mm

      Unit Weight
      TBD

      Shipping Weight
      TBD

      Shipping Dimensions
      280mm x 115mm x 2055mm

      Mounting
      G2-RACK-FOR-ZU



    Environmental

      Operating Temperature/Environment
      60 C

      Operating Relative Humidity
      85%

      Operating Elevation
      0-10000ft



    Conformance

      Regulatory Approvals
      CE



Kunder, der kiggede på dette produkt, kiggede også på