Raritan PX3-4469V

SPHINX i Europa
DK
  • AT
  • BE
  • DK
  • FR
  • DE
  • IE
  • IT
  • NL
  • ES
  • SE
  • CH
  • UK
Produktgrupper > Power Management > Raritan PX3-4469V

Raritan PX3-4469V

Monitored rack power distribution unit
(0U [vertical], 7.4kVA, 20 outlets)

Raritan PX3-4469V
6133_19408.png
6133_19409.jpg
6133_19410.jpg
  • beskrivelsebeskrivelse
  • yderligere informationyderligere information
  • PDFPDF

Monitored rack power distribution unit (0U [vertical], 7.4kVA, 20 outlets).


INPUT:
230v, 32a - IEC 60309 2P+E 6h 32A plug (2P3W);

OUTPUT:
16@ C13, 4@ C19 outlets;
on 2@ 1-pole, 16a Overcurrent Protectors;

FEATURES:
Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet, per breaker/fuse, per outlet;
Color, matrix LCD display : Voltage, current, or active power (per line, per breaker, or per receptacle / outlet);
Alarms;
Configuration information (name, ratings, IP / Networking information).
Auto-flip orientation;
Field-Replaceable, hot-swappable network module with 536MHz processor, 16MB SPI Flash, and 64MB DDR2 RAM;
Gigabit(10/100/1000) Ethernet port.
Secondary, redundant Ethernet port.
Redundant power sharing between network modules.
Remote network monitoring via HTML, JSON-RPC, SSH, Telnet, MODBUS/TCP, and SNMPv3.
Environmental monitoring [temp/humidity] capable of up to 32 sensors.
Individual outlet numbers labeled on chassis.
Automated deployment via TFTP, DHCP/PXE, SSH(CLI), or USB Flash Drives.
WiFi Capable.
USB Webcam Capable.
iPad/iPhone/Android App.
Tri-color status LED per receptacle.
Breaker metering and alarming (0V detection).
Max Dimensions 52mm x 65mm x 1298mm (2.1in x 2.6in x 51.1in).
Max Weight 4.8 kg.
Maximum ambient temperature 60C at full load.
ProdGrafik

Features

Energy Metering
Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor

Metering Accuracy
ISO/IEC 62053-21 1%

Remote Outlet Switching
No

Metering per input line
Yes for all models

Metering per Branch Circuit Breaker
Yes

Environmental Sensor Ready
Yes

Compatible Sensors
Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure.

Cascading
Yes, Max 16 PDUs can be daisy chained using a USB or Ethernet connection.

Networking
(10/100/1000 Base T) Ethernet, Secondary redundant (10/100 Base T) Ethernet.
Optional WiFi (802.11 a/b/g/n).

Onboard Display
Color, matrix LCD display : Voltage, current, or active power (per line, per breaker, or per receptacle / outlet);
Alarms;
Configuration information (name, ratings, IP / Networking information).
Auto-flip orientation



Specifications

    Input

      Input Plug
      IEC 60309 2P+E 6h 32A (2P3W)

      Nominal Voltage
      230V

      Maximum Input Current
      32A

      Rated Input Current
      32A

      Power Capacity
      7.4kVA

      Cord Length
      3m



    Output

      Nominal Voltage
      230V

      Receptacles (Output Connections)
      (16) IEC320 C13
      (4) IEC320 C19

      Overload Protection
      (2) LEGBXA6-16



    Physical

      Dimensions (WxDxH)
      2.1in x 2.6in x 51.1in;
      52mm x 65mm x 1298mm

      Unit Weight
      4.8 kg

      Shipping Weight
      6.7 kg

      Shipping Dimensions
      280mm x 115mm x 1573mm

      Mounting
      G2-RACK-FOR-ZU



    Environmental

      Operating Temperature/Environment
      60 C

      Operating Relative Humidity
      85%

      Operating Elevation
      0-10000ft



    Conformance

      Regulatory Approvals
      CE