Raritan PX2-2516
Monitored and switched rack power distribution unit
(400V, 3Ö Wye, 11.1kVA, 16A)
Monitored and switched rack power distribution unit
(400V, 3Ö Wye, 11.1kVA, 16A)
Features
- Energy Metering
Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor
Metering Accuracy
ISO/IEC 62053-21 1%
Remote Outlet Switching
Yes
Metering per input line
Yes for all models
Metering per Branch Circuit Breaker
No
Environmental Sensor Ready
Yes
Compatible Sensors
Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure.
Cascading
Yes, Max 16 PDUs can be daisy chained using a USB connection.
Note: Firmware version 3.3.10 or above is required.
Networking
10/100/1000 BaseT Ethernet.
Optional WiFi (802.11a/b/g/n).
Onboard Display
3-digit LED user-selectable display (voltage, current, or active power : per line).
Auto-flip orientation.
Specifications
- Input
- Input Plug
IEC 60309 3P+N+E 6h 16A (4P5W)
Nominal Voltage
400V
Maximum Input Current
16A
Rated Input Current
16A
Power Capacity
11.1kVA
Cord Length
3m
Output
- Nominal Voltage
230V
Receptacles (Output Connections)
(21) IEC320 C13
(3) IEC320 C19
Overload Protection
NA
Physical
- Dimensions (WxDxH)
2.1in x 2.6in x 60.6in; 52mm x 65mm x 1539mm
Unit Weight
4 kg
Shipping Weight
6 kg
Shipping Dimensions
280mm x 115mm x 1655mm
Mounting
G2-RACK-FOR-ZU
Environmental
- Operating Temperature/Environment
50 C
Operating Relative Humidity
85%
Operating Elevation
0-10000ft
Conformance
- Regulatory Approvals
CE