Raritan PX3-1909U-N2P1V2
Monitored rack power distribution unit
(0U [vertical], 22.2kVA, 48 outlets).
Monitored rack power distribution unit (0U [vertical], 22.2kVA, 48 outlets).
INPUT:
400v (3-phase WYE), 32a - IEC 60309 3P+N+E 6h 32A plug (4P5W);
OUTPUT:
36@ C13
12@ C19 outlets,
on 6@ 1-pole, 16a Overcurrent Protectors;
FEATURES:
Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet, per breaker/fuse;;
Color, matrix LCD display : Voltage, current, or active power (per line or per breaker);
Alarms;
Configuration information (name, ratings, IP / Networking).;
Auto-flip orientation
10/100/1000 Ethernet port.
Max Dimensions 89mm x 65mm x 1780mm (3.5in x 2.6in x 70.1in).
Max Weight TBD kg.
Maximum ambient temperature 60C at full load.
Features
- Energy Metering
Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor
Metering Accuracy
ISO/IEC 62053-21 1%
Remote Outlet Switching
No
Metering per input line
Yes for all models
Metering per Branch Circuit Breaker
Yes
Environmental Sensor Ready
Yes
Compatible Sensors
Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure.
Cascading
Yes, Max 16 PDUs can be daisy chained using a USB or Ethernet connection.
Networking
(10/100/1000 Base T) Ethernet, Secondary redundant (10/100 Base T) Ethernet.
Optional WiFi (802.11 a/b/g/n).
Onboard Display
Color, matrix LCD display : Voltage, current, or active power (per line or per breaker);
Alarms;
Configuration information (name, ratings, IP / Networking information).
Auto-flip orientation
Specifications
- Input
- Input Plug
IEC 60309 3P+N+E 6h 32A (4P5W)
Nominal Voltage
400V
Maximum Input Current
32A
Rated Input Current
32A
Power Capacity
22.2kVA
Cord Length
3m
Output
- Nominal Voltage
230V
Receptacles (Output Connections)
(36) IEC320 C13
(12) IEC320 C19
Overload Protection
(6) LEGBXA6-16
Physical
- Dimensions (WxDxH)
3.5in x 2.6in x 70.1in; 89mm x 65mm x 1780mm
Unit Weight
TBD kg
Shipping Weight
TBD kg
Shipping Dimensions
370mm x 160mm x 2110mm
Mounting
RACK-KIT-PX3-0U
Environmental
- Operating Temperature/Environment
60 C
Operating Relative Humidity
85%
Operating Elevation
0-10000ft
Conformance
- Regulatory Approvals
CE
Kunder, der kiggede på dette produkt, kiggede også på