MOXA NDR Power Supply Series

SPHINX i Europa
DK
  • AT
  • BE
  • DK
  • FR
  • DE
  • IE
  • IT
  • NL
  • ES
  • SE
  • CH
  • UK
Produktgrupper > Power Supplies > MOXA NDR Power Supply Series

MOXA NDR Power Supply Series

120/240 W small form factor power supply for DIN-rail mounted products

MOXA NDR Power Supply Series
7118_28357.png
7118_28358.jpg
  • egenskaberegenskaber
  • beskrivelsebeskrivelse
  • yderligere informationyderligere information
  • PDFPDF
  • DIN-rail mounted power supply
  • Slim form factor that is ideal for cabinet installation
  • Universal AC power input
  • High power conversion efficiency
The NDR Series of DIN rail power supplies is designed specifically for use in industrial applications. The 40 to 63 mm slim form-factor enables the power supplies to be easily installed in small and confined spaces such as cabinets. The broad operating temperature range of -20 to 70°C means they are capable of operating in harsh environments. The NDR Series has an AC input range from 90 VAC to 264 VAC, and conforms to the EN 61000-3-2 standard. In addition, these power supplies feature constant current mode to provide overload protection.
ProdGrafik

SPECIFICATION

    Output Power Parameters

      Wattage
      NDR-120-24: 120 W
      NDR-120-48: 120 W
      NDR-240-48: 240 W

      Voltage
      NDR-120-24: 24 VDC
      NDR-120-48: 48 VDC
      NDR-240-48: 48 VDC

      Current Rating
      NDR-120-24: 0 to 5 A
      NDR-120-48: 0 to 2.5 A
      NDR-240-48: 0 to 5 A

      Ripple and Noise
      NDR-120-24: 120 mVp-p
      NDR-120-48: 150 mVp-p
      NDR-240-48: 150 mVp-p

      Voltage Adjustment Range
      NDR-120-24: 24 to 28 VDC
      NDR-120-48: 48 to 55 VDC
      NDR-240-48: 48 to 55 VDC

      Setup/Rise Time at Full Load
      NDR-120-24: 2500 ms, 60 ms at 115 VAC
      NDR-120-24: 1200 ms, 60 ms at 230 VAC
      NDR-120-48: 2500 ms, 60 ms at 115 VAC
      NDR-120-48: 1200 ms, 60 ms at 230 VAC
      NDR-240-48: 3000 ms, 100 ms at 115 VAC
      NDR-240-48: 1500 ms, 100 ms at 230 VAC

      Typical Hold Up Time at Full Load
      NDR-120-24: 10 ms at 115 VAC
      NDR-120-24: 16 ms at 230 VAC
      NDR-120-48: 10 ms at 115 VAC
      NDR-120-48: 16 ms at 230 VAC
      NDR-240-48: 22 ms at 115 VAC
      NDR-240-48: 28 ms at 230 VAC



    Input Power Parameters

      Typical Efficiency
      NDR-120-24: 88%
      NDR-120-48: 89%
      NDR-240-48: 90%

      Typical Current
      NDR-120-24: 1.3 A @ 230 VAC, 2.25 A @ 115 VAC
      NDR-120-48: 1.3 A @ 230 VAC, 2.25 A @ 115 VAC
      NDR-240-48: 1.3 A @ 230 VAC, 2.5 A @ 115 VAC

      Voltage Range
      90 to 264 VAC (47 to 63 Hz)
      127 to 370 VDC

      Inrush Current (cold start)
      35 A @ 230 VAC, 20 A @ 115 VAC



    Overload Protection

      Rated Output Power
      105 to 160%

      Protection Type
      Constant current limiting, recovers automatically after fault condition is removed



    Overvoltage Protection

      Over-Voltage Range
      NDR-120-24: 29 to 33 V
      NDR-120-48: 56 to 65 V
      NDR-240-48: 56 to 65 V

      Protection Type
      Shut down operating voltage, repower on to recover



    Standards and Certifications

      Safety
      UL 508, EN 62368-1, IEC 62368-1

      EMC
      EN 55032/24, EN 61000-3-2 Class A, EN 61000-3-3

      EMS
      IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
      IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m
      IEC 61000-4-4 EFT: Power: 2 kV

      IEC 61000-4-5 Surge: Power: 2 kV
      IEC 61000-4-6 CS: 10 V
      IEC 61000-4-8 PFMF
      IEC 61000-4-11 DIPs



    Physical Characteristics

      Dimensions
      NDR-120-24: 123.75 x 125.20 x 40 mm (4.87 x 4.93 x 1.57 in)
      NDR-120-48: 123.75 x 125.20 x 40 mm (4.87 x 4.93 x 1.57 in)
      NDR-240-48: 127.81 x 123.75 x 63 mm (5.03 x 4.87 x 2.48 in)

      Weight
      NDR-120-24: 500 g (1.10 lb)
      NDR-120-48: 500 g (1.10 lb)
      NDR-240-48: 900 g (1.98 lb)



    Environmental Limits

      Operating Temperature
      -20 to 70°C (-4 to 158°F)

      Storage Temperature
      -40 to 85°C (-40 to 185°F)

      Ambient Relative Humidity
      20 to 95% (non-condensing)

      Max. Operating Temperature at Full Load
      NDR-120-48: 45°C (113°F)
      NDR-120-24: 45°C (113°F)
      NDR-240-48: 50°C (122°F)



    MTBF

      Standards
      MIL-HDBK-217F

      Time
      NDR-120-24: 453,334 hrs
      NDR-120-48: 453,334 hrs
      NDR-240-48: 230,206 hrs